วันศุกร์ที่ 7 พฤศจิกายน พ.ศ. 2551

PilZ PNOZ X3 - Safety Relay dD at SRINUTCH ไฟฟ้า รีเลย์

PILZ PilZ pilz p i l z p n o z x 3 PnoZ X3

Emergency Stop Relays, Safety Gate Monitors


Category 4, EN 954-1
PNOZ X3


Emergency stop relay and safety
gate monitor in accordance with
VDE 0113, 11/98, EN 60204-1, 12/97
and IEC 204-1, 11/98, safety
component in accordance with the
Lift Directive 95/16/EC and EN 81-1/
1998
Features
 Monitored manual or automatic
reset can be selected
 1 semiconductor output (K1/K2)
 Each AC unit can be operated
with 24 VDC
 Safety gate function with
N/C-N/O combination
 Only dual-channel operation will
detect shorts across the input
contacts


Technical Details PNOZ X3
Electrical Data
Supply Voltage AC: 24, 42, 48, 110, 115, 120, 230, 240 V
DC: 24 V
Tolerance 85 ... 110 %
Power Consumption Approx.2.5 W/5 VA
Voltage and Current at the Input and 24 VDC, 35 mA
Reset Circuits and Feedback Control Loop
Switching Capability in accordance with
EN 60947-4-1, 10/91 AC1: 240 V/8 A/2000 VA
DC1: 24 V/8 A/200 W
EN 60947-5-1, 10/91 AC15: 230 V/5 A; DC13: 24 V/6A
(DC13: 6 cycles/min.)
Output Contacts 3 safety contacts (N/O),
1 auxiliary contact (N/C)
Contact Fuse Protection 10 A quick or 6 A slow
(EN 60947-5-1, 10/91)
Semiconductor Outputs 24 VDC/20 mA, short-circuit protected
External Supply Voltage 24 VDC ±20 %
Times
Delay-on Energisation Monitored manual reset: max. 100 ms
Auto./ manual reset: max. 0.3 s
Delay-on De-energisation With E-STOP: max. 80 ms
With power failure: max. 1 s
Recovery Time Approx. 1 s
Simultaneity channel 1/2 
Max. Supply Interruption before De-energisation Approx. 25 ms
Environmental Data
Ambient Temperature -25 ... +55 °C
Mechanical Data
Maximum Cross Section of 2 x 1.5 mm2 or 1 x 2.5 mm2
External Conductors Single-core or multi-core
with crimp connectors
Dimensions (H x W x D) 87 x 45 x 121 mm
Weight 420 g
Description
 45 mm, P-93 housing, DIN-Rail
mounting
 Positive-guided relay outputs:
– 3 safety contacts (N/O)
– 1 auxiliary contact (N/C)
 Connections for
– E-STOP button
– safety gate limit switch
– reset button
 Semiconductor output signals
ready for operation
 LEDs for channel 1, channel 2 and
power
 Increase in the number of
safety contacts available by
connecting expander modules.
Operating Modes
 Single-channel operation
 Dual-channel operation
 Automatic reset
 Monitored manual reset


General Technical Data
Unless stated otherwise in the technical details for the specific unit
Electrical Data
Frequency Range AC 50 ... 60 Hz
Residual Ripple DC 160 %
Contact Material AgSnO2
Continuous Duty 100 %
Environmental Data
EMC EN 50081-1, 01/92, EN 50082-2, 03/95
Vibration in accordance with Frequency: 10 ... 55 Hz,
EN 60068-2-6, 04/95 Amplitude: 0.35 mm
Climatic Suitability DIN IEC 60068-2-3, 12/86
Airgap Creepage DIN VDE 0110 part 1, 04/97
Ambient Temperature -10 ... +55 °C
Storage Temperature -40 ... +85 °C
Mechanical Data
Torque Setting on Connection Terminals 0.6 Nm (screws)
Mounting Position Any
Housing Material Thermoplast Noryl SE 100
Protection Mounting: IP 54
Housing: IP 40
Terminal Range: IP 20
The units were tested in accordance with the relevant standards current at
the time of development.
Order References
Type UB Order No.
PNOZ X3 24 V AC/24 V DC 774 310
PNOZ X3 42 V AC/24 V DC 774 311
PNOZ X3 48 V AC/24 V DC 774 312
PNOZ X3 110 V AC/24 V DC 774 314
PNOZ X3 115 V AC/24 V DC 774 315
PNOZ X3 120 V AC/24 V DC 774 316
PNOZ X3 230 V AC/24 V DC 774 318
PNOZ X3 240 V AC/24 V DC 774 319